Parameter Name | Parameter Value |
---|---|
Measurement range | 0~100% (mol/mol) |
Accuracy | ±0.5% (mol/mol) |
Resolution | 0.01% |
Response time | <20s |
Operating time | >10h |
Gas source pressure | (0.1~0.6) MPa |
In the maintenance and safety inspection of electrical equipment, accurately measuring various performance indicators of SF₆/N₂/CF₄ mixed gases is of great importance. The RA-912FN series integrated analyzer for mixed insulating gases, as a newly developed high-tech product, has become a leader in the market with its excellent performance and versatility.
High-performance Microprocessor: Adopting a high-performance microprocessor to ensure the accuracy and stability of measurement data.
Large-screen Color Touch Display: An intuitive and easy-to-use operation interface provides users with a smoother and more convenient experience.
Imported Sensors: Reliable imported sensors ensure accurate measurement results.
The RA-912FN series integrated analyzer for mixed insulating gases integrates multiple functions and can measure all key parameters of SF₆/N₂/CF₄ mixed gases. Whether it is the purity, mass ratio, or volume ratio of the mixed gas, it can handle them easily, fully meeting the usage requirements of various sulfur hexafluoride electrical equipment filled with gases such as N₂ or CF₄.
Fast Measurement: Fast measurement and not interfered by other gas components, better meeting on-site needs.
Real-time Compensation: Real-time flow and temperature compensation based on experimental data to ensure the accuracy of measurement results.
Intelligent Calibration: Automatically perform zero-point and slope calibration when powered on, and remind of the sensor calibration cycle, saving you time and effort.
Cross-sensitivity Removal: The sensor matrix design effectively removes cross-sensitivity interference and improves measurement accuracy.
Multi-functional in One Machine: Truly achieve multi-functional in one machine, allowing you to complete all measurement tasks without carrying multiple instruments.
Efficient and Convenient: The large-screen color touch display and intuitive operation interface make your measurement work more efficient and convenient.
Accurate and Reliable: The perfect combination of a high-performance microprocessor and imported sensors ensures accurate and reliable measurement results.
The RA-912FN series integrated analyzer for mixed insulating gases is your ideal choice for electrical equipment maintenance and safety inspection. Let's work together to create a safer and more efficient electrical environment!
Parameter Name | Parameter Value |
---|---|
Purity measurement - Measurement range | 0~100% (mol/mol) |
Purity measurement - Accuracy | ±0.5% (mol/mol) 0.01% |
Purity measurement - Resolution | 0.01% |
Purity measurement - Response time | <20s |
Oxygen measurement - Measurement range | (0~1)% |
Oxygen measurement - Accuracy | ±0.5% (mol/mol) 0.01% |
Oxygen measurement - Resolution | 0.01% |
Oxygen measurement - Response time | <40s |
Humidity measurement - Measurement range | (-80~+20)℃ |
Humidity measurement - Accuracy | ±2℃ |
Humidity measurement - Resolution | 0.1℃ |
Overall machine - Operating time | >10h |
Overall machine - Gas source pressure | (0.1~0.6) MPa |
Overall machine - Dimensions | 310mm×280mm×150mm (L×W×H) |